Governor Model: WNDTGE
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tp < Mult*TimeStep then Tp = Mult*TimeStep
- If 0.0 < Tpc < Mult*TimeStep then Tpc = Mult*TimeStep
- If 0.0 < Tw < Mult*TimeStep then Tw = Mult*TimeStep
- If 0.0 < Tpav < Mult*TimeStep then Tpav = Mult*TimeStep
- If 0.0 < Tplwi < 0.5*Mult*TimeStep then Tplwi = 0, ElseIf 0.5*Mult*TimeStep < Tplwi < Mult*TimeStep then Tplwi = Mult*TimeStep
- If 0.0 < Twowi < 0.5*Mult*TimeStep then Twowi = 0, ElseIf 0.5*Mult*TimeStep < Twowi < Mult*TimeStep then Twowi = Mult*TimeStep
- If Pmxwi < Pmnwi then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Power Control > PImax , then PImax = Power Control or if Power Control < PImin, then PImin= Power Control
Model Equations and/or Block Diagrams
Parameters:
| Trate | Turbine rating, MW |
| Usize | WTG unit size (1.5 or 3.6) |
| Spdwl | Initial wind speed, m/s |
| Tp | Pitch control constant, sec |
| Tpc | Power control time constant, sec |
| Kpp | Pitch control proportional gain |
| Kip | Pitch control integral gain |
| Kptrq | Torque control proportional gain |
| Kitrq | Torque control integral gain |
| Kpc | Pitch compensation proportional gain |
| Kic | Pitch compensation integral gain |
| PIMax | Maximum blade pitch, deg |
| PIMin | Minimum blade pitch, deg |
| PIRat | Blade pitch rate limit, deg/sec |
| PWmax | Maximum power order, pu |
| PWmin | Minimum power order, pu |
| PWrat | Power order rate limit, pu/sec |
| H | Rotor inertia constant, p.u. (on turbine MW base) |
| Nmass | 2 for 2 mass model |
| Hg | Generator rotor inertia constant, p.u. (on turb. MW base) |
| Ktg | Shaft stiffness (p.u. torque / rad) |
| Dtg | Shaft damping (p.u. torque / p.u. speed) |
| Wbase | Base mechanical speed (rad./sec.) |
| Tw | Rate limit washout time constant, sec. |
| Apcflg | Active power control enable flag |
| Tpav | Filter time constant on Pavail, sec. |
| Pa | Active power point in frequency response curve, p.u. |
| Pbc | Active power point in frequency response curve, p.u. |
| Pd | Active power point in frequency response curve, p.u. |
| Fa | Frequency value for Pa frequency response curve, p.u. |
| Fb | Frequency value for Pbc frequency response curve, p.u. |
| Fc | Frequency value for Pbc frequency response curve, p.u. |
| Fd | Frequency value for Pd frequency response curve, p.u. |
| Pmax | Maximum wind plant power, p.u. |
| Pmin | Minimum wind plant power, p.u. |
| Kwi | WINENERTIA gain; default=0; typical non-default is 10 |
| dbwi | Deadband, pu |
| Tlpwi | Low pass filter time constant, sec |
| Twowi | Washout time constant, sec |
| urlwi | Up rate limit |
| drlwi | Down rate limit |
| Pmxwi | Maximum power output, pu |
| Pmnwi | Minimum power output, pu |
| wfflg | WindFREE reactive power function flag (1=enabled) |
| Td1 | Time delay in APC output, sec |
| Tpset | Filter time constant on Pset, sec |